The units shall be
horizontal airflow as shipped and convertible to downflow. All
units shall be factory assembled, piped, internally wired and
fully charged with refrigerant. Units shall be UL listed and
carry a UL label. All units shall be factory run tested to check
cooling operation, fan and blower rotation and control or TXV
sequence.
Units shall be designed to operate at ambient temperatures
between 115°F and 55°F in cooling as manufactured. Cooling
performance shall be rated in accordance with ARI standards.
|
|
|
|
|
| |
Unit
Casing
All components shall be mounted in a weather-resistant steel
cabinet with an enamel finish. Access panels shall be provided
for unit controls and indoor coil and fans. Indoor air section
compartment shall be completely insulated with fireproof,
permanent, odorless glass fiber material.
Knockouts shall be provided for utility and control connections.
Drain connections shall be provided to accommodate indoor
water runoff.
Compressor
The compressor shall be hermetically sealed, high efficiency
Climatuff® compressors.
Internal overcurrent and over temperature protection, internal
pressure relief shall be standard. Crankcase heaters
shall be standard on all models.
Refrigeration System
All units shall have TXV in cooling and TXV in heating. Service
pressure tap ports, and a refrigerant line filter dryer shall be
standard.
Indoor Coil
Coils shall be internally finned or smooth bore 3/8" copper
tubes mechanically bonded to configured aluminum plate fin as
standard. Evaporator coil leak and pressure tested to 200 psig;
condenser coil tested to 450 psig. |
|
|
| |