The units shall be
horizontal airflow as shipped and convertible to downflow. All
units shall be factory assembled, piped,
internally wired and fully charged with R-22.
Units shall be UL listed and carry a UL label. All units shall
be factory run tested to check cooling operation, fan and blower
rotation and control sequence. Units shall be designed to
operate at ambient temperatures between 115°F and 55°F in
cooling as manufactured. Cooling performance shall be rated in
accordance with ARI standards.
|
|
|
|
|
| |
Unit
Casing
All panels shall be heavy gauge steel, gasketed and insulated.
Foil-faced fiber insulation shall be in the heater section.
Foil-faced fiber nsulation shall be in the evaporator section.
Base pan shall be heavy gauge steel. WEATHERGUARD™ exterior
corrosion resistant screws shall be used for added resistance to
rust and corrosion.
Compressor
The compressor shall be a hermetically sealed, high efficiency
Climatuff® compressor. Internal overcurrent and over temperature
protection, internal pressure relief shall be standard. Other
features include, roto lock suction and discharge refrigerant
connections, centrifugal oil pump and low vibration and noise.
Refrigeration System
All units shall have refrigerant control. Service pressure tap
ports, and a refrigerant line filter shall be standard.
Evaporator Coil — Internally enhanced 3/8-inch OD seamless
copper tubing mechanically bonded to aluminum fins, factory
pressure and leak tested at 250 to 300 psig. All units have TXV
to control refrigerant flow. |
|
|
| |