When is it necessary to provide building exhaust? Whenever an outdoor air economizer is used, a building generally requires an exhaust system. The purpose of the exhaust system is to exhaust the proper amount of air to prevent over or underpressurization of the building. The goal is to exhaust approximately 10 percent less air than the amount of outside air going into the building. This maintains a slightly positive building pressure.
 

  A building may have all or part of its exhaust system in the rooftop unit. Often, a building provides exhaust external to the air conditioning equipment. This external exhaust must be considered when selecting the rooftop exhaust system.

IntelliPak™ Rooftop units offer four types of exhaust systems:

- 100 percent modulating exhaust with Statitrac™ direct space sensing building pressurization control (with or without variable frequency drives).

- 100 percent modulating exhaust without Statitrac.

- 50 percent power exhaust.

- Barometric relief dampers.