PAQUETES > IOM |
| |
|
| |
 |
|
ReliaTel™
Control
The ECA monitors the mixed air temperature, return air
temperature, minimum position setpoint (local or remote), power
exhaust setpoint, CO2 setpoint, CO2, and ambient dry bulb/
enthalpy sensor or comparative humidity (return air humidity
against ambient humidity) sensors, if selected, to
control dampers to an accuracy of +/- 5% of stroke. The actuator
is spring returned to the closed position
any time that power is lost to the unit. It is capable of
delivering up to 25 inch pounds of torque
and is powered by 24 VAC. |
|
|
|
|
| |
RTCI
-- ReliaTel™ Trane Communication Interface (Optional)
This module is used when the application calls for an ICSTM
building management type control system. It allows the control
and monitoring of the system through an ICS panel. The
module can be ordered from the factory or ordered as a kit to
be field installed. Follow the installation instruction
that ships with each kit when field installation is necessary.
RLCI - ReliaTel™ LonTalk Communication Interface (Optional)
This module is used when the application calls for an ICSTM
building management type control system that is LonTalk. It
allows the control and monitoring of the system through
an ICS panel. The module can be ordered from the factory or
ordered as a kit to be field installed.
Follow the installation instruction that ships with each kit
when field installation is
necessary.
RTOM – ReliaTel™ Options Module (Optional)
The RTOM monitors the supply fan proving, clogged filter, supply
air temperature, exhaust fan setpoint, supply air tempering,
Frostat™ and smoke detector. Refer to system input
devices and functions for operation. |
|
|
| |
FICHA TÉCNICA
|
|
|
 |
|
| PAQUETES |
|
|
|
|
|